AO Smith® AOSHW670

AO Smith® HW-670 Water Heater, 660000 Btu/hr BTU, 120 VAC, Natural Gas Fuel, 1 in NPT, Bronze/Brass

Manufacturer: A. O. Smith Corporation
Part #: AOSHW670
Customer Part #:
Login for Availability
Login for Price
BTU Rating      :      660000 Btu/hr
Chimney/Breeching/Vent Size      :      12 in
Connection Type      :      1 in NPT
Dimensions      :      68-5/16 in H x 36-1/2 in D
Flow Rate      :      53 gpm
Frequency Rating      :      60 Hz
Fuel Type      :      Natural Gas
Material      :      Bronze/Brass
Mounting Type      :      Floor
Net BTU Rating      :      528000 Btu/hr
Pressure Rating      :      160 psi
Vent Type      :      Atmospheric
Voltage Rating      :      120 VAC

AO Smith® Water Heater, 120 VAC, 60 Hz Frequency, 660000 Btu/hr BTU, 53 gpm Flow Rate, 160 psi Pressure, 1 in NPT Connection, Natural Gas Fuel, Atmospheric Vent, Chimney/Breeching/Vent Size: 12 in, Net BTU Rating: 528000 Btu/hr, Floor Mounting, Bronze/Brass, Dimensions: 68-5/16 in H x 36-1/2 in D

  • All castings are made of bronze or brass
  • All water tubes are made from copper
  • Brazed joints or flare union construction make the boiler immune to the effects of thermal shock and thermal cycling
  • A great boiler for domestic hot water supply
  • The efficient copper coil combustion chamber is a heat exchanger formed from a two passage coil of tightly wound continuous copper tube
  • Water circulating through this coil surrounds the main burner and captures the radiant heat
  • A wrap of insulation on the outside of the coil retains the heat captured by the circulating water
  • Directly above the coil and the main burner is a compact, horizontal, copper fin tube heat exchanger
  • The flue gases must pass through this efficient heat exchanger before leaving the boiler
  • This unique Burkay® coil and heat exchanger design provide maximum heat transfer and proven field durability
  • The patented Burkay® burner uses primary air injection at up to 72 individual orifices plus secondary entrainment of air
  • Approved for installation on combustible floors as shipped from factory
  • Slow opening redundant gas valves ensure smooth light off without flame roll-out or pilot outage
  • Patented pump delay system that allows boiler and pump to run simultaneously but delays pump shut-off at end-of heating cycle to remove usable heat from the heat exchanger and reduce the scale forming tendencies of motionless hot water
  • Proven pilot ignition system provides flame failure response in under one second
  • Redundant high limit controls and gas valves assure safe shutoff in the event of overheating or flame failure
  • Requires 120 V 60 Hz, maximum inlet gas pressure of 14 in-WC and activation of boiler by external temperature control

back To Top